Bosch Rexroth VFC 610 Series Operating Instructions Manual page 33

Brake chopper
Hide thumbs Also See for Rexroth VFC 610 Series:
Table of Contents

Advertisement

Brake Chopper
B1 Conductors in installation pipes and
in installation channels that can be
opened
B2 Cables or lines in installation pipes
and in installation channels that can
be opened
Fig. 6-4: Cable installation types (cf. IEC 60364-5-52; DIN VDE 0298-4; EN 60204-1)
2. Recommendation for design of the fuses:
International except for USA / Canada: Class gL -gG; 500 V, 690 V; design
NH, D (DIAZED) or D0 (NEOZED).
Characteristics
In the case of error (e.g. ground error at connections L+, L -), fuses of
characteristic gL (general-purpose fuse link for cables and lines) and
gG (general-purpose fuse link for general installations) protect the
lines in system.
To protect the brake chopper, you can use fuses of characteristic gR.
USA / Canada: Class J; 600 V
DOK-RCON04-VFC*BRAKE**-IT01-EN-P
Bosch Rexroth AG
Brake Chopper Wiring
C
Cables or lines on walls
E
Cables or lines on open cable trays
27/65

Advertisement

Table of Contents
loading

Table of Contents