Cable Specifications; Power Cables - Bosch Rexroth VFC 610 Series Operating Instructions Manual

Brake chopper
Hide thumbs Also See for Rexroth VFC 610 Series:
Table of Contents

Advertisement

Bosch Rexroth AG
Brake Chopper Wiring

6.2 Cable Specifications

6.2.1 Power Cables

Brake chopper
model
FEAE07.1-VA1-NNNN
FEAE07.1-VA2-NNNN
Tab. 6-1: Fuse and cable dimensions for international without USA / Canada
Brake chopper
model
FEAE07.1-VA1-NNNN
FEAE07.1-VA2-NNNN
Tab. 6-2: Fuse and cable dimensions for USA / Canada
The recommended values of the fuse listed in the tables above are
based on the Max. output current, please select the proper fuse ac-
cording to the actual application.
Dimensioning variables of the table values
1. Installation types:
B1 according to IEC 60364-5-52, e.g. stranded wires routed in cable
duct
B2 according to IEC 60364-5-52, e.g. multi-core line routed in cable duct
E according to EN 60204-1, e.g. multi-core line routed on open cable tray
According to NFPA 79 (external wiring), UL 508A (internal wiring), NEC,
NFPA 70:
– 1 cable with 3 conductors, 1 neutral conductor and 1 equipment
grounding conductor
– Routed in pipe on the wall
Internal wiring: Routing inside of control cabinet or of devices.
Field wiring: Routing of cross sections of terminal connectors wired by
the user (in the field).
26/65
Power cables installation
Fuse (gG)
B1
[mm
2
] [mm
100
10.0
160
10.0
Power cables
Fuse (Class J)
[AWG]
100
175
mode
PE cable
B2
E
2
] [mm
2
]
[mm
10.0
10.0
10.0
10.0
10.0
10.0
PE cable
[AWG]
8
8
6
6
DOK-RCON04-VFC*BRAKE**-IT01-EN-P
Brake Chopper
Torque / Screw
[N·m / lb·in] (Mx)
2
]
1.76 / 15.6 (M4)
1.76 / 15.6 (M4)
Torque / Screw
[N·m / lb·in] (Mx)
1.76 / 15.6 (M4)
1.76 / 15.6 (M4)