Setting The Signal Runtime; Calibration - Pilz PSS Series Operating Manual

Hide thumbs Also See for PSS Series:
Table of Contents

Advertisement

Setting the signal runtime

To measure the length of the bus cable you will need to enter the signal
runtime. The ex-works setting for the signal runtime is 4.5 ns/m. This value
is valid for the Pilz standard cable for SafetyBUS p (order no. 311 070). If
you use a cable with a different signal runtime, you will need to amend the
set value.
• Press F2 in the "Start" window.
• The "Settings" window opens. Use the arrow keys to move the cursor to
the symbol for "Signal runtime"
• Use the arrow keys to enter the password "7041" and press VAL.
• The signal runtime is displayed. Use the arrow keys to set the signal
runtime to the required value.
• Press VAL to save the setting.
The current setting is saved. A message confirms that the setting has been
saved. The "Settings" window is then displayed again. You can return to
the "Start" window by pressing ESC.
The setting is stored in a memory that is supplied by the battery. If the
battery is removed, the contents of the memory will be retained for 10
minutes. If it takes longer for the battery to be replaced, the contents of the
memory will be lost.

Calibration

Calibration is reserved for Pilz customer service.
Operating Manual: PSS SB TESTER
and press VAL.
4-5