UPS5000-E-(60 kVA-125 kVA)
User Manual (Integrated UPS 3.0)
Figure 3-30 Connecting battery cables
A neutral wire is routed from the middle of the positive and negative battery
strings.
Take a battery string consisting of 40 batteries for example. The battery neutral
wire is routed from the middle of positive and negative battery strings, each
consisting of 20 batteries.
Figure 3-31 Battery neutral wire
Use corrugated pipes to protect cables when connecting cables. After cable
connection is complete, reinstall the removed insulation panels at the rear of the
cabinet.
----End
3.2.5.2 Routing Cables from the Bottom
Issue 04 (2022-12-30)
NO TICE
Copyright © Huawei Digital Power Technologies Co., Ltd.
3 Installation
90