UPS5000-E-(60 kVA-125 kVA)
User Manual (Integrated UPS 3.0)
Table 9-1 Physical specifications
Item
Cabling mode
IP rating
Dimensions (H x W x
D)
Communication
Table 9-2 Environmental specifications
Item
Operating temperature
Storage temperature
Humidity
Altitude
Issue 04 (2022-12-30)
9
Copyright © Huawei Digital Power Technologies Co., Ltd.

Technical Specifications

Specifications
Routed in and out from the top
Routed in and out from the bottom (tail frame
configured)
IP20
2000 mm x 600 mm x 1100 mm
2000 mm x 600 mm x 1200 mm (tail frame
configured)
Supports dry contacts, RS485 serial ports, and FE ports.
Specifications
0–40°C
–40°C to +70°C
5%–95% RH (non-condensing)
0–4000 m
When the altitude is higher than 2000 m, the power is
derated as described in IEC 62040-3. The upper limit of
the altitude is 4000 m.
9 Technical Specifications