UPS5000-E-(60 kVA-125 kVA)
User Manual (Integrated UPS 3.0)
Figure 2-31 Flipping the Motor/Manual selection lever
Step 5 Check whether the Power LED and Auto LED indicators are on, as shown by (1) in
Figure
operation mode.
Step 6 If the Auto LED indicator is off, press the Auto button once. Then the controller
enters the automatic operation mode, as shown in
Figure 2-32 Automatic mode
----End
Manual Mode
Step 1 Turn on the circuit breakers of the ATS operation mechanism (Q1 and Q2 in the
left lower part at the rear of the cabinet) to power on the ATS operation
mechanism.
Step 2 Check whether the ATS controller has alarms. If an alarm exists, rectify the fault
first.
Step 3 Flip the Motor/Manual selection lever to the Man. position.
Issue 04 (2022-12-30)
2-32. If the Auto LED indicator is on, the controller is in the automatic
Copyright © Huawei Digital Power Technologies Co., Ltd.
2 Product Overview
Figure
2-32.
56