Huawei UPS5000-E-60 kVA User Manual page 148

Hide thumbs Also See for UPS5000-E-60 kVA:
Table of Contents

Advertisement

UPS5000-E-(60 kVA-125 kVA)
User Manual (Integrated UPS 3.0)
Item
Br. cur. shock
protect (%)
X Harmonics,
Y Harmonics,
Z Harmonics
Harmonic
alarm enable
System
overfrequency
threshold
(Hz)
Mains
overfrequency
alarm enable
Mains
underfrequen
cy alarm
enable
Branch
breaker open
alarm enable
Issue 04 (2022-12-30)
Description
Branch current surge
protection alarm threshold.
When the percentage of the
branch current to the rated
branch current exceeds the
threshold, an alarm is
generated.
The system can display three
types of harmonics based on
the settings.
Specifies whether to enable
harmonic alarms. If this
parameter is set to Enable,
an alarm (voltage/current
harmonic alarm) is
generated when the alarm
condition is met.
When the system frequency
is higher than the rated
frequency plus the value of
this parameter or is lower
than the rated frequency
minus the value of this
parameter, the system
generates an alarm.
If this parameter is set to
Enable, an alarm is
generated when the alarm
condition is met.
If this parameter is set to
Enable, an alarm is
generated when the alarm
condition is met.
If this parameter is set to
Enable, the system generates
an alarm when the branch
circuit breaker opens. If this
parameter is set to Disable,
the system does not generate
the alarm under any
condition.
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 LCD Interface
Default Value
Value Range
300
150–500
X harmonics: 5
2–63
Y harmonics: 7
Z harmonics:
11
Disable
Disable,
Enable
1.5
1.0-10
Enable
Disable,
Enable
Enable
Disable,
Enable
Enable
Disable,
Enable,
Custom
140