UPS5000-E-(60 kVA-125 kVA)
User Manual (Integrated UPS 3.0)
3.1.2.2 Installation Environment
●
●
●
●
3.1.2.3 Installation Clearances
Reserve the following clearances around the cabinets to facilitate operations and
ventilation:
●
●
●
Figure 3-2 Reserved clearances (unit: mm)
3.1.3 Preparing Power Cables
Issue 04 (2022-12-30)
Do not install the UPS in a high-temperature, low-temperature, or damp place
that is beyond the technical specifications.
Keep the UPS far away from water, heat sources, and flammable and
explosive substances. Install the UPS in an environment free of dust, volatile
gas, salt, and corrosive materials. Avoid direct sunlight.
Do not install the UPS in environments with conductive metal scraps in the
air.
The optimal operating temperatures for valve-regulated lead-acid (VRLA)
batteries are 20–30°C. Operating temperatures higher than 30°C shorten the
battery lifespan, and operating temperatures lower than 20°C reduce the
battery backup time.
Reserve a clearance of at least 800 mm from the front of the cabinets for
ventilation and operations.
Reserve a clearance of at least 800 mm from the rear of the cabinet for
ventilation and operations.
Reserve a clearance of at least 500 mm from the top of the cabinets for
operations.