User Manual (Integrated UPS 3.0)
Step 11 Reinstall the protective panel.
----End

8.3 Replacing a Circuit Breaker

The UPS does not need to be powered off because the circuit breakers are hot
swappable.
Procedure
Step 1 Switch off the faulty circuit breaker and remove the circuit breaker protective
cover.
Step 2 Push open the handles on both sides of the circuit breaker and remove the circuit
breaker using a jig.
Figure 8-6 Removing a circuit breaker
Step 3 Remove the copper bar and install it on the new circuit breaker.
Figure 8-7 Removing the copper bar
Step 4 Switch off the new circuit breaker, install it using a jig, and close the handle.
Issue 04 (2022-12-30)
NO TE
Remove and install the circuit breaker using a jig. Do not operate barehanded.
Copyright © Huawei Digital Power Technologies Co., Ltd.
8 Parts Replacement
191