Huawei UPS5000-E-60 kVA User Manual page 188

Hide thumbs Also See for UPS5000-E-60 kVA:
Table of Contents

Advertisement

UPS5000-E-(60 kVA-125 kVA)
User Manual (Integrated UPS 3.0)
Check Item
Battery
appearance
Battery
operating
temperature
Battery string
charging
voltage
Issue 04 (2022-12-30)
Expected Result
1. The surface is clean and
tidy without stains.
2. The battery terminals are
intact.
3. Batteries are free from
damage and cracks.
4. Batteries are free from acid
leakage.
5. Batteries are not deformed
or bulged.
1. The ambient temperature
of batteries is 25±5°C.
2. The battery operating
temperature must be lower
than the ambient
temperature plus 20°C.
3. Battery charge and
discharge conditions meet
the requirements specified
in the battery
specifications.
● Equalized charging voltage
(2.35 V/cell±1%) x Voltage
of a single battery/2 x
Number of batteries in a
battery string
● Float charging voltage
(2.25 V/cell±1%) x Voltage
of a single battery/2 x
Number of batteries in a
battery string
Copyright © Huawei Digital Power Technologies Co., Ltd.
6 Routine Maintenance
Troubleshooting
If an exception occurs, contact
technical support.
1. Identify the cause of an
abnormal battery operating
temperature.
2. If the fault persists, contact
technical support.
1. If the voltage drop between
the battery string output
terminals and the battery
input terminals at the UPS
side is greater than 1% of
the battery string voltage,
check whether the cable
between the battery string
and the UPS is excessively
long, or the cable diameter
is excessively small.
2. Check whether the
equalized charging voltage
and float charging voltage
are correctly set for the
UPS.
3. If the fault persists, contact
technical support.
180