Initial Startup - Huawei UPS5000-E-60 kVA User Manual

Hide thumbs Also See for UPS5000-E-60 kVA:
Table of Contents

Advertisement

UPS5000-E-(60 kVA-125 kVA)
User Manual (Integrated UPS 3.0)
Procedure
Step 1 Switch on the MCCB (skip this step in the case of ATS input).
Step 2 Switch on the UPS input circuit breaker QF1.
The UPS is powered by the mains and initialization begins. The LCD displays an
initialization progress bar.
----End

5.3.2 Initial Startup

If the equipment is started for the first time, obtain authorization for the
equipment and set related parameters on the Settings Wizard screen. If the
equipment is not started for the first time, skip this section.
Procedure
Step 1 Obtain the startup password through the app. After the application is approved,
enter the password on the service authorization screen of the device to complete
device authorization.
Technical support engineers can obtain the service authorization code through the
app. For details, see the
Step 2 Set the language, time and date, network parameters, system parameters, and
battery parameters on the Settings Wizard screen.
Set system parameters with caution. Incorrect setting may affect the normal UPS
operation.
● Set Single/Parallel after double check. Incorrect settings may affect the normal
● Output voltage level refers to the line voltage level. Set it based on site
● Set Output frequency correctly. Otherwise, loads may be affected and the UPS
● Set all battery parameters correctly based on site requirements. Battery
Issue 04 (2022-12-30)
NO TICE
NO TICE
NO TICE
UPS operation.
requirements.
may not work properly.
parameter settings are critical to battery maintenance, battery lifespan, and
UPS discharge time.
Copyright © Huawei Digital Power Technologies Co., Ltd.
Data Center Facility Deployment Guide .