Protection and Automation Functions
5.26 78VS Voltage Vector Shift
of the 78 pickup setting. A setting of 6° is recommended by the G.59 standard for connection of distributed
generation to an electricity supply system, and settings of 8° to 12° are typical.
When the exported power to the mains network is very low, there is a risk that the drop in load will be insuffi-
cient to cause a vector shift, or will cause a vector shift of limited extent. Generally it is required that exported
power will be of the order of 10 % to 20 % of total power generated before a LOM will always be detected.

Settings Menu

5.26.5
Functions > Function Config
Parameter
78VS Vector Shift
Functions > Protection > 78VS > Gn 78VS-n
Parameter
Element
Setting

IEC 61850 Functional Information Mapping

5.26.6
A78VSPPAM*.Mod
Information
78VS Vector Shift Enabled (Function Config)
Element Disabled
Element Inhibited
A7VS8PPAM*.Mod.stVal
Device Annunciation ON/TRUE: 1
IEC 61850 Value
A78VSPPAM *.Health
Information
Device Healthy
A78VSPPAM*.Health.stVal
340
Range
Enabled
Disabled
Range
Enabled
Disabled
2° to 30°, Δ 0.5°
OFF/FALSE: 0
Irrelevant: x
ON: 1
BLOCKED: 2
TEST: 3
TEST/BLOCKED: 4
OFF: 5
Settings
Default Gn1
Gn2
Disabled
Settings
Default Gn1
Gn2
Disabled
10°
x
0
1
x
x
x
5
5
0
3
Reyrolle 7SR5, Overcurrent Protection Device, Device Manual
C53000-G7040-C014-1, Edition 11.2019
Gn3
Gn4
Gn3
Gn4
1
1
0
0
1
0
2
1
1
1