Iec 61850 Functional Information Mapping - Siemens 7SR51 Device Manual

Overcurrent protection device
Table of Contents

Advertisement

Protection and Automation Functions
5.17 51 Time-Delayed Overcurrent – Phase
Functions > Protection > 51 > Gn 51CL-n
Parameter
Char
Time Mult (IEC/ANSI)
Delay (DTL)
Min Operate Time
Follower DTL
Reset

IEC 61850 Functional Information Mapping

5.17.6
A51PTOC*.Mod
Information
51 Overcurrent Enabled (Function Config)
Element Disabled
Element Inhibited
A51PTOC*.Mod.stVal
Device Annunciation ON/TRUE: 1
IEC 61850 Value
A51PTOC*.Health
Information
Device Healthy
A51PTOC*.Health.stVal
Device Annunciation ON/TRUE: 1
IEC 61850 Value
264
Setting Options
DTL
IEC-NI
IEC-VI
IEC-EI
IEC-LTI
ANSI-EI
ANSI-MI
ANSI-VI
0.01 to 1.6, Δ 0.01
1.6 to 5, Δ 0.1
5 to 100, Δ 1
0 to 20 s Δ 0.01 s
0 to 20 s Δ 0.01 s
0 to 20 s Δ 0.01 s
IEC/ANSI Decaying
0 to 60 s Δ 1 s
OFF/FALSE: 0
Irrelevant: x
ON: 1
BLOCKED: 2
TEST: 3
TEST/BLOCKED: 4
OFF: 5
OFF/FALSE: 0
OK: 1
WARNING: 2
ALARM: 3
Settings
Default Gn1
Gn2
IEC-NI
1
5 s
0 s
0 s
0 s
x
0
1
x
x
x
5
5
0
3
Reyrolle 7SR5, Overcurrent Protection Device, Device Manual
C53000-G7040-C014-1, Edition 11.2019
Gn3
Gn4
1
1
0
0
1
0
2
1
1
1