Iec 61850 Functional Information Mapping - Siemens 7SR51 Device Manual

Overcurrent protection device
Table of Contents

Advertisement

Functions > Protection > 59N > Gn 59NIT-n
Parameter
Delay
Reset

IEC 61850 Functional Information Mapping

5.23.6
A59NITPTOV*.Mod
Information
59N Overvoltage Enabled (Function Config)
Element Disabled
Element Inhibited
A59NITPTOV*.Mod.stVal
Device Annunciation ON/TRUE: 1
IEC 61850 Value
A59NITPTOV*.Health
Information
Device Healthy
A59NITPTOV*.Health.stVal
Device Annunciation ON/TRUE: 1
IEC 61850 Value
A59NITPTOV*.Op
Information
Element Operated
A59NITPTOV*.Op.general
Device Annunciation ON/TRUE: 1
IEC 61850 Value
Reyrolle 7SR5, Overcurrent Protection Device, Device Manual
C53000-G7040-C014-1, Edition 11.2019
Range
0 to 20 s Δ 0.01 s
IEC/ANSI Decaying
0 to 60 s Δ 1 s
OFF/FALSE: 0
Irrelevant: x
ON: 1
BLOCKED: 2
TEST: 3
TEST/BLOCKED: 4
OFF: 5
OFF/FALSE: 0
OK: 1
WARNING: 2
ALARM: 3
OFF/FALSE: 0
TRUE: 1
FALSE: 0
Protection and Automation Functions
5.23 59N Neutral Voltage Displacement
Settings
Default Gn1
Gn2
5 s
x
0
1
x
x
x
5
5
0
3
0
0
Gn3
Gn4
1
1
0
0
1
0
2
1
1
1
1
1
317