Protection and Automation Functions

5.8 46BC Broken Conductor Detection

5.8
46BC Broken Conductor Detection

Overview of Functions

5.8.1
The Broken Conductor Detection function is used to:
Detect open circuit primary conductors on 1 or 2 phases
Provide an alarm for indication purposes

Structure of the Function

5.8.2
The broken conductor detection function element has group dependent settings. These settings can be
different in each settings group – group numbers (Gn) 1 to 4.
This function corresponds to the logical node A46BCPTOC* in IEC 61850.
The function monitors the primary system using the 3 phase current inputs e.g. CT1/2/3. The fundamental
frequency component is measured from processing of the measured current samples.
The broken conductor in a 3 phase system is detected by a high the ratio of the negative phase sequence
(NPS) current level to positive phase sequence (PPS) current level