Calculation of Required Stability Voltage Limits
The assigned through fault current is 31.5 kA.
[fo_function87GHApplication&SettingsFunction13, 1, en_US]
[fo_function87GHApplication&SettingsFunction14, 1, en_US]
[fo_function87GHApplication&SettingsFunction15, 1, en_US]
Calculation of Stabilizing Resistor Value
The required relay setting I
[fo_function87GHApplication&SettingsFunction21, 1, en_US]
[fo_function87GHApplication&SettingsFunction22, 1, en_US]
[fo_function87GHApplication&SettingsFunction23, 1, en_US]
The magnetizing current is dependent on the relay operate voltage (V
sional value is chosen from the above i.e. 107.1 < V
Say V
= 120 V. From CT magnetizing curve: At 120 V I
setprov
[fo_function87GHApplication&SettingsFunction24, 1, en_US]
[fo_function87GHApplication&SettingsFunction25, 1, en_US]
Metrosil Specification
C Value
V
= 120 V (i.e. > 100 V) so a C value of 1000 is chosen
set
Short Time Power Rating
Using the empirical formula
[fo_function87GHApplication&SettingsFunction12, 1, en_US]
Reyrolle 7SR5, Overcurrent Protection Device, Device Manual
C53000-G7040-C014-1, Edition 11.2019
can be calculated from:
set
set
Protection and Automation Functions
5.29 87GH Restricted Earth-Fault Protection – High-Impedance
). This is not finalized yet so a provi-
set
< 150
= 9 mA and I
MAGLCT
MAGNCT
= 12 mA
361