Undercurrent Earth Fault - Measured - Siemens 7SR51 Device Manual

Overcurrent protection device
Table of Contents

Advertisement

Phase
CT1(I
)
A
CT2(I
)
B
CT3(I
)
C
Element Blocking
The undercurrent elements can be blocked by Binary Input Inhibit. This functionality should be
checked.
Element
37-1
37-2
Element Blocking from Current Guard
The elements can be blocked by the undercurrent guard function. This functionality should be checked.
Element
37-1
37-2
Check correct phase indication, trip output, alarm contacts, waveform record.
9.9.6
37G Undercurrent Earth Fault – Measured
If 2 undercurrent 37G elements are used with different settings, it is convenient to test the element with the
lowest setting first. The higher setting element can then be tested without interference from the other
element.
Apply current to the single phase input at a level above the undercurrent 37G-n setting until the element
resets.
If DTL setting is small, gradually reduce current until element operates.
If DTL is large apply 1.1 times setting, check for no operation, apply 0.9 times setting, check operation.
Apply 0.5 times setting current and record operating time.
Phase
CT4(I
)
G
Element Blocking
The undercurrent elements can be blocked by Binary Input Inhibit. This functionality should be
checked.
Element
37G-1
37G-2
Element Blocking from Current Guard
The elements can be blocked by the undercurrent guard function. This functionality should be checked.
Element
37G-1
37G-2
Reyrolle 7SR5, Overcurrent Protection Device, Device Manual
C53000-G7040-C014-1, Edition 11.2019
I
(Amps)
DTL (sec)
set
Guard Setting
I
(Amps)
DTL (sec)
set
Guard Setting
P.U. Current
Tolerence
Amps
BI Inhibits
Blocked
P.U. Current
Tolerence
Amps
BI Inhibits
Blocked
Functional Tests
9.9 Protection Functional Tests
Op. Time 0.5 ⋅
Tolerance
I
set
Op. Time 0.5 ⋅
Tolerance
I
set
469