Iec 61850 Functional Information Mapping - Siemens 7SR51 Device Manual

Overcurrent protection device
Table of Contents

Advertisement

Protection and Automation Functions
5.22 59 Overvoltage Protection – 3 Phase
Functions > Protection > 59 > Gn 59 Common
Parameter
Input Selection
Functions > Protection > 59 > Gn 59-n
Parameter
Element
Pickup Option
Setting
Hysteresis
Delay
VTS Inhibit
5.22.6

IEC 61850 Functional Information Mapping

A59PTOV*.Mod
Information
59 Overvoltage Enabled (Function Config)
Element Disabled
Element Inhibited
A59PTOV*.Mod.stVal
Device Annunciation ON/TRUE: 1
IEC 61850 Value
A59PTOV*.Health
Information
Device Healthy
A59PTOV*.Health.stVal
310
Range
Ph-Ph
Ph-N
Range
Enabled
Disabled
Any
All
1 to 200 V, Δ 0.5 V
0 to 80 %, Δ 1 %
0 to 20 s Δ 0.01 s
20 to 100 s Δ 0.1 s
100 to 1000 s Δ 1 s
1000 to 10000 s Δ 10 s
10000 to 14400 s Δ 100 s
No
Yes
OFF/FALSE: 0
Irrelevant: x
ON: 1
BLOCKED: 2
TEST: 3
TEST/BLOCKED: 4
OFF: 5
Settings
Default Gn1
Gn2
Ph-Ph
Settings
Default Gn1
Gn2
Disabled
Any
80 V
3 %
0.1 s
No
x
0
1
x
x
x
5
5
0
3
Reyrolle 7SR5, Overcurrent Protection Device, Device Manual
C53000-G7040-C014-1, Edition 11.2019
Gn3
Gn4
Gn3
Gn4
1
1
0
0
1
0
2
1
1
1

Advertisement

Table of Contents
loading

This manual is also suitable for:

Reyrolle 7sr5

Table of Contents