Iec 61850 Functional Information Mapping - Siemens 7SR51 Device Manual

Overcurrent protection device
Table of Contents

Advertisement

Functions > Protection > 51GS > Gn 51GS-n
Parameter
Reset
VTS Action
9
79 Delayed Inhibit

IEC 61850 Functional Information Mapping

5.19.6
A51GSPTOC*.Mod
Information
51GS Sensitive EF Enabled (Function Config)
Element Disabled
Element Inhibited
A51GSPTOC*.Mod.stVal
Device Annunciation ON/TRUE: 1
IEC 61850 Value
A51GSPTOC*.Health
Information
Device Healthy
A51GSPTOC*.Health.stVal
Device Annunciation ON/TRUE: 1
IEC 61850 Value
A51GSPTOC*.Op
Information
Element Operated
A51GSPTOC*.Op.general
Reyrolle 7SR5, Overcurrent Protection Device, Device Manual
C53000-G7040-C014-1, Edition 11.2019
Setting Options
IEC/ANSI Decaying
0 to 60 s Δ 1 s
Off
Inhibit
Non-Dir
No
Yes
OFF/FALSE: 0
Irrelevant: x
ON: 1
BLOCKED: 2
TEST: 3
TEST/BLOCKED: 4
OFF: 5
OFF/FALSE: 0
OK: 1
WARNING: 2
ALARM: 3
Protection and Automation Functions
5.19 51GS Time-Delayed Sensitive Earth Fault – Measured
Settings
Default Gn1
Gn2
0 s
Off
No
x
0
1
x
x
x
5
5
0
3
0
0
Gn3
Gn4
1
1
0
0
1
0
2
1
1
1
1
1
283