6.3 GBMS function panel and definition

Figure 6.3-1 GBMS description
Table 6.3-1 GBMS panel function definition description
Item
Designation
1
CBMS interface
2
LAN
3
Dial switch
4
DC24V-IN
5
CAN
6
RS485
7
Dry contact
8
HMI update
9
ON/OFF
10
Indicator
11
SD card
SHENZHEN CENTER POWER TECH CO., LTD
Address: Rooms 9-12, 7F, Block B, Building 7, Zone 2, Shenzhen Bay Technological and
Ecological Park, Nanshan District, Shenzhen, China
Tel: 0755-66851118 Fax: 0755-66850678 Email: sales@vision-batt.com
Description
The connector port with CBMS
LAN interface
Reserved function
Supply power port to GBMS
Communicate port with UPS
Communicate port with UPS
Input dry contact I1,Output dry contact D1~3
D1:NO
D2:NO
D3:NO
I1:NO
Update the HMI interface
GBMS DC power supply switch
GBMS running indicate
GBMS running data store 10000 records
Green Our Earth
Power Your Vision
Remarks
CAN Communication
Updating GBMS program
GBMS in parallel
Supplied by CBMS
CAN2.0
Mod bus RTU protocol
D1: Charger shutdown signal
D2: No discharge signal
D3: Secondary protection signal
I1:EPO(input) When EPO active open