10.7 UPS Parameter Setting

Item
Description
2 Battery Block per string
4 Battery block capacity
5 Recommended charging current
6
Float Voltage(V)
7
Boost Voltage(V)
8
EOD Voltage(V)

11 Running Test

11.1 Starting up examination

11.1.1 START-UP CHECKLIST

Obtain a copy of the customer sales order number being worked.
Verify with the sales order that the correct units were shipped.
o Check the CBMS & with System GBMS
o Check the CBMS & without System GBMS
Inventory the shipment to ensure all parts were shipped and there is no shipping damage or part
shortages.
Before installing into the cabinet, check the insulation resistance of the battery module.
Note: Refer to Insulation Resistance Test Manual.
Install all components (CBMS, battery modules, GBMS, Cabinet,communication cables, etc.).
SHENZHEN CENTER POWER TECH CO., LTD
Address: Rooms 9-12, 7F, Block B, Building 7, Zone 2, Shenzhen Bay Technological and
Ecological Park, Nanshan District, Shenzhen, China
Tel: 0755-66851118 Fax: 0755-66850678 Email: sales@vision-batt.com
Value
40
50/100/40/200 AH Lithium Module No is 10
50/100/40/200Ah
Depends on the batteries cabinet
0.2C-0.5C
54*n
n=Lithium batteries module Qty in cabinets
54.4(55.2)*n
n=Lithium batteries module Qty in cabinets
44.8*n
n=Lithium batteries module Qty in cabinets
Green Our Earth
Power Your Vision
Remarked
50AH cabinet:10A-25A
100AH cabinet :20-50A
40AH cabinet:8A-20A
200AH cabinet:40A-100A