Vision REVO User Manual page 105

Lithium battery system
Hide thumbs Also See for REVO:
Table of Contents

Advertisement

Table 11.2-2 Troubleshooting list
Fault type
Cause
The voltage in the system exceeds the
Over voltage
maximum setting DC value.
The DC voltage in the system is below the
Under voltage
minimum setting value.
The system charging current exceeds the
Charging over current
maximum setting current
A short circuit occurs in the master control
Discharging over current
CBMS, or its internal components are
damaged.
Module
Low temperature
charging
minimum charging temperature.
Low temperature
The module temperature is below the
discharging
minimum discharging temperature
SHENZHEN CENTER POWER TECH CO., LTD
Address: Rooms 9-12, 7F, Block B, Building 7, Zone 2, Shenzhen Bay Technological and
Ecological Park, Nanshan District, Shenzhen, China
Tel: 0755-66851118 Fax: 0755-66850678 Email: sales@vision-batt.com
Process mode
1、Check whether the charging voltage of the UPS terminal is reasonable. If the
charging voltage of UPS exceeds the setting value, please contact the UPS
manufacturer for solution.
2、Check the maximum setting voltage of battery terminal, and check the protection
parameters setting through LCD or VISION APP.
Check the minimum setting voltage of the battery terminal, and check the protection
parameters setting through LCD or VISION APP.
1. Check whether the charging current of the UPS terminal is reasonable. If the
charging current of UPS exceeds the setting value, please contact the UPS
manufacturer for solution.
2. Check the maximum setting charging current at the battery end, and check the
protection parameters setting through LCD or VISION APP.
1. Check whether the output power of UPS terminal is overloaded, and whether the
actual power conforms to the setting value. If the output power of UPS exceeds the
setting value, please contact UPS manufacturer for solution.
2、Check whether there is any problem with the internal control circuit of the master
control CBMS. Please also contact our company.
Check whether the indoor environment temperature is reasonable. If it is, check the
minimum charging temperature parameters set in the system, and check the
temperature
is
below
the
protection parameters setting through LCD or VISION APP. When the temperature
rises to the reasonable value, the battery will be recharged. After the above process,
if the same problem repeats, completely power off the system and then check the
battery module.
Check whether the indoor environment temperature is reasonable. If it is, check the
minimum discharging temperature parameters set in the system, and check the
protection parameters setting through LCD or VISION APP. When the temperature
rises to the reasonable value, the battery will be recharged and discharged. After the
above process, if the same problem repeats, completely power off the system and
then maintain the battery module.
Green Our Earth
Power Your Vision
105

Advertisement

Table of Contents
loading

Table of Contents