DEEP SEA ELECTRONICS DSE8610 MKII Operator's Manual page 174

Table of Contents

Advertisement

Fault
MSC Alarms Inhibited
MSC 1 and 2 Failure
MSC 1 Data Error
MSC 1 Link Failure
MSC 1 Too Few Sets
MSC 2 Data Error
MSC 2 Link Failure
MSC 2 Too Few Sets
Negative Phase Sequence
IEEE C37.2 - 46 Phase-Balance
Current Relay
Oil Pressure Low
IEEE C37.2 - 63 Pressure Switch
Protections Disabled
SCR Inducement
Water in Fuel
Wet Stacking
057-254 ISSUE: 10
Protections
Description
The module detected that an input configured for MSC Alarms
Inhibit had become active disabling all the MSC alarms.
That module detected that the MSC and Redundant MSC
communication failed, most likely caused by it being disconnected.
The module detected that data on the MSC link had become
corrupt, possibly caused by incorrect wiring or faulty cabling.
That module detected that the MSC communication failed, most
likely caused by it being disconnected.
That module detected that the number of modules on the MSC was
less than the configured Minimum Modules on MSC Link setting.
The module detected that data on the Redundant MSC link had
become corrupt, possibly caused by incorrect wiring or faulty
cabling.
That module detected that the Redundant MSC communication
failed, most likely caused by it being disconnected.
That module detected that the number of modules on the
Redundant MSC was less than the configured Minimum Modules
on MSC Link setting.
The module detected that there was an imbalance of current
across the generator phases greater than the Negative Phase
Sequence Trip Level percentage setting.
The module detected that the engine oil pressure had fallen below
the Low Oil Pressure Pre-Alarm Trip level after the Safety On
Delay timer had expired.
The module detected that an input configured for Protections
Disable became active.
The module received a fault condition from the engine ECU alerting
about the SCR Inducement.
The module received a fault condition from the engine ECU alerting
that water in the fuel had been detected or that the Water in Fuel
input switch had activated.
The module detected that the generator output kW had fallen below
the Low Load Alarm Trip level for the configured delay timer.