DEEP SEA ELECTRONICS DSE8610 MKII Operator's Manual page 169

Table of Contents

Advertisement

Fault
2131 ID 1 to 4 Analogue
Input A to J Low
2131 ID 1 to 4 Analogue
Input A to J
2133 ID 1 to 4 Analogue
Input A to H High
2133 ID 1 to 4 Analogue
Input A to H Low
Analogue Input A to D
(Digital)
Battery Detect Failure
Battery Failure Detection
Output 1
Battery Failure Detection
Output 2
Battery High Current
Output 1
Battery High Current
Output 2
Battery High Temperature
Output 1
Battery High Temperature
Output 2
Continued over page...
Protections
Description
NOTE: Due to module configuration the alarm message
that appears on the display may be different. For further details
of module configuration, refer to DSE Publication: 057-238
DSE8610 MKII Configuration Suite PC Software Manual.
The module detected that an analogue input value of a DSE2131
had fallen below the Flexible Sensor Low Pre-Alarm Trip level.
NOTE: Due to module configuration the alarm message
that appears on the display may be different. For further details
of module configuration, refer to DSE Publication: 057-238
DSE8610 MKII Configuration Suite PC Software Manual.
The module detected that a digital input configured to create a fault
condition on a DSE2131 expansion module became active and the
appropriate LCD message displayed.
NOTE: Due to module configuration the alarm message
that appears on the display may be different. For further details
of module configuration, refer to DSE Publication: 057-238
DSE8610 MKII Configuration Suite PC Software Manual.
The module detected that an analogue input value of a DSE2133
had risen above the Flexible Sensor High Pre-Alarm Trip level.
NOTE: Due to module configuration the alarm message
that appears on the display may be different. For further details
of module configuration, refer to DSE Publication: 057-238
DSE8610 MKII Configuration Suite PC Software Manual.
The module detected that an analogue input value of a DSE2133
had fallen below the Flexible Sensor Low Pre-Alarm Trip level.
NOTE: Due to module configuration the alarm message
that appears on the display may be different. For further details
of module configuration, refer to DSE Publication: 057-238
DSE8610 MKII Configuration Suite PC Software Manual.
The module detected that an analogue input configured as a digital
input to create a fault condition became active and the appropriate
LCD message is displayed.
The module detected that a battery charger connected by DSENet
had issued a Battery Detect Failure alarm.
The module detected that a battery charger connected by DSENet
had issued a Battery Failure Detection alarm on its Output 1.
The module detected that a battery charger connected by DSENet
had issued a Battery Failure Detection alarm on its Output 2.
The module detected that a battery charger connected by DSENet
had issued a Battery High Current alarm on its Output 1.
The module detected that a battery charger connected by DSENet
had issued a Battery High Current alarm on its Output 2.
The module detected that a battery charger connected by DSENet
had issued a Battery High Temperature alarm on its Output 1.
The module detected that a battery charger connected by DSENet
had issued a Battery High Temperature alarm on its Output 2.
Page 169 of 246
®
®
®
®
®
®
®
057-254 ISSUE: 10