Whilst the generators are in parallel, the DSE8x10 controllers instruct the generators to run at a
certain frequency/voltage dependant on the active power (kW)/reactive power (kvar) the generator is
producing. In the example below, both generators have the same Droop Curve configured for the
Frequency Droop and Voltage Droop. Even though one generator is twice the size of the other, both
generators are producing 80 % of their kW rating at 50.5 Hz and 40 % of their kvar rating at 412 V.
This occurred as the Droop Curve for the Frequency Droop and Voltage Droop was configured the
same in both generators.
106
105
104
103
102
101
100
99
98
0
10
20
Generator Rating:
100 kW
75 kvar
50 Hz
400 V
Operation
5% Droop Curve with 5% Offset
30
40
50
60
70
Total Power (%)
Site Load:
240 kW
90 kvar
Generator Output:
80 kW
(80
%)
30 kvar
(40
%)
50.5 Hz
(101
%)
412 V
(103
%)
Page 149 of 246
80
90
100 110
Generator Output:
160 kW
(80
%)
60 kvar
(40
%)
50.5 Hz
(101
%)
412 V (103%)
Droop Curve
Frequency/kW Relation
Voltage/kvar Relation
Generator Rating:
200 kW
150 kvar
50 Hz
400 V