ForceDoor BASE70 Instructions And User Manual page 28

Industrial door drive control system
Table of Contents

Advertisement

XH06-1 Relay output
module function setting
The buzzer turns off.
Remark:
The buzzer turns off.(default)
Press and hold SET button for about 6
seconds to enter main menu until "0.-"
appears on the display then release the
button.
Press "+" till "6.-" appears on the
display.
Press SET then appears "6.0" on the
display
Press "+" till "6.6" appears on the
display.
Press SET enter into XH06-1 Relay
output module function setting. (Refer
to page - 36 Relay module output
terminal)
Reach the open limit position, relay closed
Reach the close limit position, relay closed
Reach the partial open limit position, relay
closed
Before the door drive running, the relay is
closed first (1-7 seconds time adjustable)
Press SET to confirm and directly enter the
time setting. Adjust the stalls from
to
default:Represents 3 seconds.
Relay always closed during the door drive
running. After the door drive stops, relay
will be disconnected after 1-10 minutes
delay.(Adjustable time, similar to courtesy
light OFF DELAY function).
Press SET to confirm and directly enter the
26
by buttons +/-.