March 2023
Table 9-3: Input Parameters
Special Conditions for Safe Use (X):
1. The apparatus is not capable of withstanding the 500 V
insulation test required by clause 6.3.12 of EN60079-11: 2012.
This must be taken into account when installing the apparatus.
2. The enclosure may be made of aluminum alloy and given a
protective polyurethane paint finish; however, care should be
taken to protect it from impact or abrasion if located in Zone 0.
9.6.4  N1 ATEX Type n and Dust
Certificate
Standards
Markings
Special Conditions for Safe Use (X):
1. This apparatus is not capable of withstanding the 500 V
insulation test that is required by clause 6.8.1 of EN60079-15.
This must be taken into account when installing the apparatus.
2. Some variants of the equipment have reduced markings on
the nameplate. Refer to the Certificate for full equipment
marking.
9.7 
International
9.7.1  E7 IECEx Flameproof and Dust
Certificate
Standards
Quick Start Guide
Voltage U
i
Current I
i
Power P
i
Capacitance C
i
Inductance L
i
BAS00ATEX3105X; Baseefa11ATEX0275X
EN60079-0:2012 + A11:2013, EN60079-15:2010,
EN60079-31:2014
II 3 G Ex nA IIC T5 Gc (–40 °C  ≤ T
II 1 D Ex ta IIIC T95 °C T
+85 °C)
IECEx KEM 09.0034X; IECEx BAS 10.0034X
IEC 60079-0:2017, IEC 60079-1:2014-06, IEC
60079-26:2014-10, IEC 60079-31:2013
Quick Start Guide
Fieldbus/PROFIBUS
17.5 V
380 mA
5.32 W
≤ 5 nF
≤ 10 µH
≤ +70 °C);
a
105 °C Da (–20 °C ≤ T
500