ELECTRICAL WIRING DIAGRAMS
ADDING REFRIGERANT
Refrigerant must be added if the pipe length is more than 5 metres (16'5"). This
operation can only be performed by a professional F-Gas engineer, for the additional
gas amount, see the below
Liquid pipe
diameter
Φ6.3 or Φ6 (1/4)
Φ9.52 or Φ9 (3/8)
GAS LEAKAGE INSPECTION
After the pipeline connection is done, use a leakage inspection device to carefully check
if there is any leakage at the joints. This is an important step to ensure the quality of
installation. Once a leak is detected, proper action should be taken immediately.

INSTALL THE WATER DRAINAGE PIPE

1. For good drainage, the drain hose should be angled downwards.
2. Do not pull on or bend the drain hose or flood its end with water.
3. When the long drainage hose passes through indoor areas, it should be wrapped in
insulation.
Additional
Refrigerant
15g per each meter
added
25g per each meter
added
Additional Refrigerant
(Total length of pipe run – 5 meters) x 15 g
(Total length of pipe run – 5 meters) x 25 g
33