4. Initial Start-up

Verify that all AC, DC and Alarm connections are complete and secure. Once this is complete, the AC
input breakers may be turned on. If rectifiers have not yet been installed, install rectifiers now as
described in Section 3. As each rectifier is installed, the controller automatically identifies the new
rectifier and begins communication.
If there are no alarms, make any adjustments to the default settings on the controller that are
required for this installation. The following steps cover the minimum configuration of the controller.
Refer to the controller sections in Pulsar Controller Manual (167-792-183), comcode CC848815341, for
issues like web pages, craft port and changes to settings. Most functions in software are intuitive by
referring to the menu map listed in Appendix A.

Minimum Controller Configuration

The controller is preconfigured for Central Standard Time and the following float voltage related
settings. If these standard defaults are OK, no configuration is required. Refer to the table below to
change these defaults. For more advanced operations, please see the Advanced Features User Guide
for the Pulsar Plus Controller.
Alarm
Float Voltage
Very High Voltage
Major
High Voltage
Minor
BD (Battery on Discharge)
Major
Very Low Voltage
Major
Page 29
© 2021 ABB. All rights reserved.
The factory default setting is 54.5V
Alarm occurs and the unit is shut down when the system detects voltage above its
set threshold. The threshold can be set from 50V to
60V in 1V increments. The factory default setting is 57V
Alarm indicates an abnormally high output voltage but does not shut the unit down.
The alarm threshold can be set from 50V to 60V in 1V
increments. The factory default setting is 56V.
Alarm occurs when the system is operating either completely or partially on battery
power. The alarm threshold can be set from 46V
to 55V in 0.1V increments. The factory default setting is 51.0V.
Alarm indicates an imminent system shutdown due to discharging batteries or low
output voltage. The factory default setting is -46.0V.