Local Port (Rs-232 / Usb) Connection - ABB CPS6000-Systems-48V DC Power Installation Manual

Table of Contents

Advertisement

Local Port (RS-232 / USB) Connection

This isolated RS-232/USB serial port is used for local PC access or for connection to an external
modem. The software interface is compatible with Lineage Power EasyView for Windows GUI
software for PCs. Software support is also provided for use with Lineage Power Galaxy Manager for
web-based remote access and monitoring. You can download EasyView
Click the Downloads button. Select EasyView Monitoring Software.
Using LAN Port for PC Access
The local craft port requires that you use EasyView software. To access the controller from a PC using
only your web browser, use the LAN port. The following steps change the LAN connection from the
Client (Network) mode to the Server (Local) mode.
Warning: It is always safer to restore the controller in Client mode. This avoids LAN conflicts should
the controller ever be connected to a Local Area Network. As good policy, always restore the
controller to Client mode.
Step
Action
1.
Press Menu or Accept key,
2.
Press down arrow, ▼ , to Configuration.
3.
Press the right arrow key,
4.
Press down arrow, ▼, to Communications Ports.
5.
Press the right arrow key,
6.
Press down arrow, ▼, to Network Settings.
7.
Press the right arrow key,
8.
Press down arrow, ▼, to highlight DHCP.
9.
Press the right arrow key,
10.
Press down arrow, ▼, to toggle to SERVER.
11.
Press save,
12.
Press the Back Arrow,
13.
Wait 2 minutes.
14.
Activate changes by removing the latching PWR connection, located on the lower right of the controller,
until the LEDs extinguish.
15.
Reapply power by reinserting the PWR connection until latched.
16.
Verify Server Mode by pressing Menu>Status>Network Settings>Port 1> to find 192.168.2.1 as the network
address.
17.
Launch the PC's internet browser and enter 192.168.2.1 in the address bar.
Page 26
© 2021 ABB. All rights reserved.
.
(or square "accept" key, ) to advance.
(or square "accept" key,
(or square "accept" key, ) to advance.
(or square "accept" key, ) to advance.
.
, to return to the default screen.
CP:S6000_External Distribution_IG
atabbpowerconversion.com
) to advance.
Rev. 1.3

Advertisement