ABB CPS6000-Systems-48V DC Power Installation Manual page 30

Table of Contents

Advertisement

Configuration Attribute to
Step
1.
NOTE:
Please note that the system will validate the entries before the system date is modified.
2.
3.
Page 30
© 2021 ABB. All rights reserved.
Change
Date
Format
This field allows you to select one of the following date formats: MM/
DD/YY, DD/MM/YY, YY/MM/DD, MM/DD/YYYY, DD/MM/YYYY,
YYYY/MM/DD. Use the
<+> or <-> key to select the desired format and press
<ENTER> to save the change.
Month
Use this field to change the month; the possible value is from 1 to 12.
Day
Use this field to change the day of the month; the possible value is
from 1 to 31.
Year
Use this field to change the year; the possible value is from 1992 and
up.
Time
Format
This field allows you to select one of the following time display
formats: 12 or 24 hour. Use the <+> or <-> key to select desired format
and press <ENTER> to save the change.
Time
Allows you to change/set the time.
Daylight
Enables or Disables Daylight Savings per the new standards created
by the Energy Policy Act of 2001. (Started in 2007.)
Batteries
Type
The configuration of this field selects the battery type, Flooded or Valve
Regulated (sealed). This parameter is used in reserve time prediction
and enhanced battery test features. Move the cursor to the field and
use the <+> or <-> key to adjust the threshold value. Press <ENTER> to
save the change. Note that the controller will ask to confirm the
corresponding float voltage settings.
CP:S6000_External Distribution_IG
Menu Path/Action
Configuration
Shunt Monitors
System Settings
Date
Time
Rev. 1.3

Advertisement

Table of Contents
loading

Table of Contents