Step 8 - Initial Startup

Verify that all AC, DC, GND and Controller connections are complete and secure.
Using a multimeter, Verify plant reference ground and chassis ground resistance to side ground bar is less than
0.1 Ohms. With rectifiers and converters unplugged as well as all load breakers on and AC breakers off, verify
resistance of battery bus to ground is greater than 1MΩ. If being operated as an ungrounded system, verify both
positive and negative bus measurement to each other and ground is greater than 1MΩ.
Turn on AC input breakers. If there are no alarms, make required adjustments to the default settings on the
controller for this installation.

Step 9 - Configure Controller

Verify and edit controller basic configuration parameters per site engineering instructions.
Refer to Galaxy Pulsar Plus Product Manual for additional information.
Information: Controller Default Voltage Settings
Parameter
Rectifier Float Selective High Voltage Shutdown
High Float Voltage Major Alarm
High Float Voltage Minor Alarm
Rectifier/System Float Voltage
Battery on Discharge Float Alarm
Very Low Float Voltage Alarm
Rectifier On Threshold
Information: AC Cord Options
IEC-Style, 8ft, 12AWG
Part Number
CC848847368
CC848850792
CC848850801
CC848850826
CC848850834
CC848850842
850044361
850044362
CC848895961
Information: Battery Monitoring Connections
Battery Monitoring is accomplished with a "Daisy Chained" series of probes connected to J2. The Probes monitor
battery temperature and voltage (ES771 required to monitor voltage). Bolt the Probe under the "–" terminal
connector hardware; NOT under the connecting lug.
Temperature Measurement
Page 5
© 2020 ABB. All rights reserved.
Range
-50 to -60V
-50 to -60V
-50 to -60V
-42 to -56.5V
-46 to -55V
-40 to -51V
-40 to -51V
Length
Plug
8 ft
No plug
8 ft
5-15P
8 ft
5-20P
8 ft
6-15P
8 ft
6-20P
L6-20P
8 ft
15 ft
L5-15P
15 ft
L5-20P
15 ft
L6-20P
Valve-Reg (Default)
58.50
57.00
56.00
54.48
51.00
46.00
44.00
Molex mini-fit SR-Style, No Plug
CC848822420
848710711
CC848830522
CC848773515
CC848906586
Temperature and Voltage Measurement
Flooded
NiCd
58.50
58.50
57.00
57.00
56.00
56.00
52.08
54.40
50.00
51.00
46.00
46.00
44.00
44.00
(2) 15 ft., 3X8AWG
(2) 10 ft., 3X8AWG
(2) 4 ft., 3X8AWG
15 ft., 10AWG SO Cord
10 ft., 8AWG, SO Cord

Advertisement

Table of Contents
loading

Table of Contents