ABB CPS6000-Systems-48V DC Power Installation Manual page 31

Table of Contents

Advertisement

Configuration Attribute to
Step
Float Voltage
From the default screen,
press the Display Menu key
to see the Main Menu.
4.
Press the down arrow key
until Configuration is
highlighted, press the
Display Menu key and the
following selections are
available; Float settings,
Shunt rating, Rectifier
Redundancy, Batteries,
Contactors, Boost, System
Settings, and
Communication Ports.
The Float Settings option
will be highlighted, press
the Display Menu key to
access the Float Settings
Menu.
The Set Point option will be highlighted. Press the Display Menu key to view or change the Float voltage Set
Point. Use the left and right arrow keys to adjust the Set Point voltage. Once
the Voltage has been set to the desired value Press the Display Menu key to save the change. The voltage
range is 42.0 to 56.5 Volts. Factory default is -54.5V.
Select Voltage Alarms to set the four Voltage Alarm thresholds.
Page 31