Transportation Packaging; Locating The Horizon; Clearances To Combustible Materials - Osburn OB04010K Installation And Operation Manual

Table of Contents

Advertisement

6.3.2 Transportation packaging

To facilitate transportation of the HORIZON fireplace before installation, we have designed a transportation
packaging that allows reducing the weight. The fireplace refractory panels are in a box you can carry
separately. We suggest you install the refractory panels after the setting up of the fireplace. To install the
refractory panels, see Appendix 5 - Refractory Slabs Replacement.

6.3.3 Locating the HORIZON

The best location to install your fireplace is determined by considering the location of windows, doors, and
the traffic flow in the room where the fireplace is located, allowing space in front of the unit for the heart
extension and the mantel, and taking into consideration the location of the hot air ducts (optional), outside
air kit and chimney. If possible, choose a location where the vent will not interfere with any truss, roof
beams, wall studs, water pipes or electrical wiring. It may be easier to relocate the fireplace than to rework
the building structure. Also choose a location that allows installing the least amount of offsets in the
chimney.
Usually, no additional floor support is needed for the fireplace. The adequacy of the floor can be checked by
first estimating the weight of the fireplace system. Weights are given in the section 2.2 - General features.
Next, measure the area occupied by the fireplace which is normally 50 3/4" X 26 7/8" (128.9 cm x 68.6 cm).
Note the floor construction and consult your local building code to determine if additional support is
needed.
THE FIREPLACE MUST BE INSTALLED ON A LEVEL AND STRAIGHT (NOT UNEVEN) SURFACE.

6.3.4 CLEARANCES TO COMBUSTIBLE MATERIALS

The clearances shown in this section have been determined by test according to procedures set out in
safety standards ULC-S610 (Canada) and UL127 (U.S.A.). When the fireplace is installed so that its surfaces
are at or beyond the minimum clearances specified, combustible surfaces will not overheat under normal
and even abnormal operating conditions.
NO PART OF THE FIREPLACE MAY BE LOCATED CLOSER TO COMBUSTIBLES THAN THE MINIMUM
CLEARANCE FIGURES GIVEN.
34
WARNING
WARNING
HORIZON – Installation and Operation Manual