Salicru EQUINOX EQX2 4002-T User Manual page 21

Three-phase solar inverters connected to the grid
Hide thumbs Also See for EQUINOX EQX2 4002-T:
Table of Contents

Advertisement

1.
Steps for connecting the AC connector.
a.
Remove the AC connector from the accessory bag.
b.
The fully disassembled AC connector is shown below:
AC terminal head
Fig. 33. AC connector.
c.
According to the above table, select a suitable cable,
remove the insulation sleeve from the AC cable about
50  mm, and remove the insulation from the end of the
L/PE/N cables about 8 mm, as shown in Fig. 34:
Cable diameter: 10-14 mm.
Fig. 34. Cable stripping.
d.
Insert the stripped end of the three cables into the
corresponding hole of the terminal head (yellow-green
cable into the PE port, phase into the L port and neutral
into the N port). Pull from the cable to check that it is
properly connected, as shown in Fig. 35:
Fig. 35. Inserting the bare wire into the terminal.
e.
According to the direction of the arrow, push the threaded
sleeve until it connects to the AC terminal head, and then
turn the cable gland clockwise to lock it, as shown in Fig. 36:
Fig. 36. Connecting and fastening the sleeve on the
AC terminal.
USER MANUAL
Threaded sleeve
Cable gland
Str i p p ed l e n g th : 8 mm.
50 mm.
f.
Connect the AC connector to the inverter's AC terminal;
a click indicates that the connection is in place, as shown
in Fig. 37:
Fig. 37. Connecting the AC connector to the inverter's AC terminal.
g.
Insert the relevant AC circuit breakers in between,
as shown in the table below:
Model
Differential
EQX2 4002-T
EQX2 5002-T
4p 25 A 30 mA
Class A
EQX2 6002-T
EQX2 8002-T
EQX2 10002-T
4p 32 A 30 mA
EQX2 12002-T
Class A
EQX2 15002-T
EQX2 17002-T
4p 40 A 30 mA
Class A
EQX2 20002-T
EQX2 25002-T
4p 50 A 30 mA
Class A
EQX2 33004-T
4p 63 A 30 mA
Class A
EQX2 40004-T
4p 80 A 30 mA
Class A
EQX2 50004-T
4p 100 A 30
mA Class A
EQX2 100010-T
4p 160 A 30
mA Class A
Tab. 10. AC circuit breakers
Previous
Over-voltage
fuse.
protection
Max. value
(1/phase)
Type II 40 kA
125 A gL
400 V TNC
EQX2 SOLAR INVERTERS CONNECTED TO THE GRID