Rcd Testing; General Data; Contact Voltage; Trip-Out Time - METREL EurotestXE MI 3102H Instruction Manual

Table of Contents

Advertisement

MI 3102H

9.3 RCD testing

9.3.1 General data

Nominal residual current................... 10 mA, 30 mA, 100 mA, 300 mA, 500 mA,
Nominal residual current accuracy.... -0 / +0.1 ⋅ I
Test current shape............................ Sine-wave (AC), pulsed (A)
RCD type .......................................... general (G, non-delayed), selective (S, time-
delayed)
Test current starting polarity ............. 0
Voltage range ................................... 100 V ÷ 264 V (45 Hz ÷ 65 Hz)
RCD test current selection (r.m.s. value calculated to 20 ms) according to IEC 61009:
½ × I
AC
I
(mA)
ΔN
10
5
30
15
100
50
300
150
500
250
1000
500
*)
not available

9.3.2 Contact voltage

Measuring range according to EN61557-6 is 3.0 V ÷ 49.0 V for limit contact voltage 25
V.
Measuring range according to EN61557-6 is 3.0 V ÷ 99.0 V for limit contact voltage 50
V.
Measuring range (V)
0.0 ÷ 9.9
10.0 ÷ 99.9
Accuracy applies for 1 year in reference conditions. Temperature coefficient outside
these limits is +1 digit.
Test current ...................................... max. 0.5 × I
Limit contact voltage ......................... 25 V, 50 V
Fault loop resistance at contact voltage is calculated as

9.3.3 Trip-out time

Complete measurement range corresponds to EN61557-6 requirements. Specified
accuracies are valid for complete operating range.
1000 mA
-0.1 ⋅ I
0
1 × I
ΔN
ΔN
A
AC
A
3,5
10
20
10,5
30
42
35
100
141
105
300
424
175
500
707
350
1000
1410
Resolution (V)
0.1
0.1
, 2 × I
; I
= I
Δ
Δ
ΔN
= ½ × I
/ +0; I
Δ
Δ
ΔN
0
or 180
2 × I
ΔN
AC
A
20
40
60
84
200
282
600
848
1000
1410
*)
2000
(-0 % / +10 %) of reading + 2 digits
(-0 % / +10 %) of reading
ΔN
R
L
76
Technical specifications
, 5 × I
ΔN
ΔN
5 × I
ΔN
AC
A
50
100
150
212
500
707
*)
1500
*)
2500
*)
*)
Accuracy