Voltage And Frequency - METREL EurotestXE MI 3102H Instruction Manual

Table of Contents

Advertisement

MI 3102H
Check the displayed warnings and online voltage/terminal monitor.
Step 3
Continuous test is running. Actual result is shown on the display during test.
All three-phase voltages are displayed in order of their sequence represented
by the numbers 1, 2 and 3.
Figure 5.42: Example of phase sequence test result
Displayed results:
Ph ...........Phase sequence,
1.2.3........Correct connection,
2.3.1........Invalid connection,
-.-.- ..........Irregular voltages.
Save displayed results for documentation purposes. Refer to chapter 6.1.
Saving results.

5.7 Voltage and frequency

Voltage measurement should be carried out often while dealing with electric installations
(carrying out different measurements and tests, looking for fault locations, etc.).
Frequency is measured for example when establishing the source of mains voltage
(power transformer or individual generator).
How to perform voltage and frequency measurement
Select VOLTAGE function with the function selector switch. The following
Step 1
menu is displayed:
Figure 5.43: Voltage and frequency measurement menu
Connect test cable to the EurotestXE 2,5 kV instrument.
Follow the connection diagram shown in figure 5.44 to perform voltage and
Step 2
frequency measurement.
54
Measurements