Technical data
7.4 Option modules
 
Auxiliary power
Connecting to circuits with the fol‐
lowing peak values
Effective internal capacitance
Effective internal inductance
Galvanic isolation
Test voltage
Rated condition height
7.4.6

Internal NCS module 6DR4004-5L / 6DR4004-5LE

Additional modules
 
Linearity (after corrections made by
positioner)
Hysteresis
For connecting to circuits with the fol‐
lowing peak values
Effective internal capacitance
Effective internal inductance
74
Without explosion pro‐
tection
U
 ≤ DC 35 V
Aux
I ≤ 20 mA
-
-
-
The 3 outputs are galvanically isolated from the basic device
Max. 2 000 m above sea
level.
At altitudes greater than
2 000 m above sea level,
use a suitable power sup‐
ply.
Without explosion pro‐
tection
6DR4004-5L
-
-
-
With explosion protec‐
tion Ex "ia", "db ia"
-
U
 ≤ 15 V
i
I
 ≤ 25 mA
i
P
 ≤ 64 mW
i
C
 ≤ 5.2 nF
i
L
 = negligibly small
i
3150 V DC, 2 s
-
With explosion protec‐
tion
Ex "ia", "db ia"
6DR4004-5LE
± 1 %
± 0.2 %
U
 ≤ 5 V
i
I
 ≤ 160 mA
i
P
 ≤ 120 mW
i
C
 = 110 nF + 110 nF per meter of connecting cable
i
L
= 270 µH + 6.53 µH per meter of connecting cable
i
Compact Operating Instructions, 11/2022, A5E03436620-AG
With explosion protec‐
tion Ex "ic", "tb"
-
"ic" :
U
 ≤ 15 V
i
I
 ≤ 25 mA
i
"tb":
U
 ≤ 15 V
n
I
 ≤ 25 mA
n
C
 ≤ 5.2 nF
i
L
 = negligibly small
i
-
With explosion protec‐
tion
Ex "ic", "ec", "tb"
6DR4004-5LE
U
 ≤ 5 V
i