Manual Initialization Of Linear Actuators - Siemens SIPART PS2 Operating Instructions Manual

Hide thumbs Also See for SIPART PS2:
Table of Contents

Advertisement

4. Set the "3.YWAY" parameter to determine the total stroke in mm. The setting of parameter 3
is optional. The display shows the determined total stroke at the end of the initialization
phase.
– Press the
– Call the "3.YWAY" parameter. To do this, press
5. Call the "4.INITA" parameter. To do this, briefly press the
following:
6. Start the initialization process. To do this, keep the
until the display shows the following:
The positioner runs through several initialization steps during the automatic initialization
process. The lower line of the display indicates which initialization step is currently being run
through. The initialization process depends on the actuator used, and takes up to 15 minutes.
7. The following display indicates that the initialization is complete:
5.6.3

Manual initialization of linear actuators

See detailed operating instructions for information on manual initialization of linear actuators.
SIPART PS2 (6DR5...)
Compact Operating Instructions, 11/2022, A5E03436620-AG
button if you do not require any information about the total stroke in mm. You
then reach parameter 4.
Note
Set the "3.YWAY" parameter
1. On the scale of the lever, read the value marked by the carrier pin.
2. Set the parameter with the buttons
5.6 Commissioning linear actuators
. The display shows the following:
and
to the read value.
button. The display shows the
button pressed for at least 5 seconds
Commissioning
47