Technical data
7.4 Option modules
Effective internal capacitance
Effective internal inductance
1 digital input current circuit
•
Digital input DI2: Terminals 11 and 12, terminals 21 and 22 (jumper)
•
Galvanically connected with the
basic device
Signal status 0
Signal status 1
Contact load
•
Electrically isolated from the basic
device
Signal status 0
Signal status 1
Internal resistance
•
Static destruction limit
•
Connecting to circuits with the fol‐
lowing peak values
Effective internal capacitance
Effective internal inductance
Galvanic isolation
Test voltage
7.4.2
Analog Output Module (AOM) 6DR4004-6J / -8J
Direct current output for position feed‐
back
1 current output, terminals 61 and 62
•
Rated signal range
•
Dynamic range
•
Auxiliary power supply U
•
External load R
[kΩ]
B
70
Without explosion pro‐
tection or suitable for use
in Ex "db" version
6DR4004-8A
-
-
± 35 V
-
-
-
The three digital outputs, the DI1 digital input and the basic device are galvanically
Without explosion pro‐
tection or suitable for use
in Ex d version
6DR4004-8J
+12 ... +35 V
Aux
With explosion protec‐
tion Ex "ia", "db ia"
6DR4004-6A
C
≤ 5.2 nF
i
L
= negligibly small
i
Floating contact, open
Floating contact, closed
3 V, 5 μA
≤ 4.5 V or open
≥ 13 V
≥ 25 kΩ
-
U
≤ 25.2 V DC
i
C
= negligibly small
i
L
= negligibly small
i
isolated from each other.
DC 840 V, 1 s
With explosion protec‐
tion Ex "ia", "db ia"
6DR4004-6J
2-wire connection
4 ... 20 mA, short-circuit proof
3.6 ... 20.5 mA
+12 ... +30 V
≤ (U
[V] - 12 V)/I [mA]
Aux
Compact Operating Instructions, 11/2022, A5E03436620-AG
With explosion protec‐
tion
Ex "ic", "ec", "tb"
6DR4004-6A
C
≤ 5.2 nF
i
L
= negligibly small
i
-
"ic":
U
≤ 25.2 V DC
i
"ec"/"tb":
U
≤ 25.2 V DC
n
C
= negligibly small
i
L
= negligibly small
i
With explosion protec‐
tion
Ex "ic", "ec", "tb"
6DR4004-6J
+12 ... +30 V
SIPART PS2 (6DR5...)