Inductive Limit Switches (Ils) 6Dr4004-6G / -8G - Siemens SIPART PS2 Operating Instructions Manual

Hide thumbs Also See for SIPART PS2:
Table of Contents

Advertisement

Technical data
7.4 Option modules
 
 
Static destruction limit
Signal 10 V
Rated signal range
Internal resistance R
i
Static destruction limit
Supply and signal power circuits
7.4.4

Inductive Limit Switches (ILS) 6DR4004-6G / -8G

 
 
Limit encoder with slotted initiators
and fault message output
2 slotted initiators
Digital output 1: Terminals 41 and 42
Digital output 2: Terminals 51 and 52
Connection
Signal state High
(not triggered)
Signal state Low (triggered)
2 slotted initiators
Function
Connecting to circuits with the fol‐
lowing peak values
Effective internal capacitance
Effective internal inductance
 
1 fault message output
Digital output: Terminals 31 and 32
Connection
Signal state High
(not triggered)
72
Without explosion
protection
6DR4004-8F
40 mA
 
0 ... 10 V
25 kΩ
20 V
Galvanically connected with the basic device
Without explosion pro‐
tection
6DR4004-8G
 
2-wire technology in accordance with EN 60947-5-6 (NAMUR), for switching amplifi‐
NC contact (NC, normally closed)
Rated voltage 8 V, power
consumption:
≥ 3 mA (limit not activa‐
ted),
≤ 1 mA (limit activated)
-
-
At switching amplifier in accordance with EN 60947-5-6: (NAMUR), U
R = 1.1 kΩ
With explosion protec‐
tion
Ex "ia", "db ia", "ic"
6DR4004-6F
 
With explosion protec‐
tion Ex "ia", "db ia"
6DR4004-6G
 
ers connected on load side
> 2.1 mA
< 1.2 mA
Type SJ2-SN
U
 ≤ DC 15 V
i
I
 ≤ 25 mA
i
P
 ≤ 64 mW
i
C
 ≤ 161 nF
i
L
 ≤ 120 μH
i
 
1 kΩ).
> 2.1 mA
Compact Operating Instructions, 11/2022, A5E03436620-AG
With explosion protec‐
tion
Ex "ec", "tb"
6DR4004-6F
-
-
-
-
With explosion protec‐
tion Ex "ic", "ec", "tb"
6DR4004-6G
 
"ic":
U
 ≤ DC 15 V
i
I
 ≤ 25 mA
i
"ec"/"tb":
U
 ≤ DC 15 V
n
P
 ≤ 64 mW
n
C
 ≤ 161 nF
i
L
 ≤ 120 μH
i
= 8.2 V, R
Aux
i
> 2.1 mA
SIPART PS2 (6DR5...)
=

Advertisement

Table of Contents
loading