Introduction; Document Organization; Tips, Important Notes, Cautions, And Warnings; Listings - Bosch D8128D Installation Manual

Octopopit module
Hide thumbs Also See for D8128D:
Table of Contents

Advertisement

1.0

Introduction

The D8128D OctoPOPIT Module combines the functions of the D8125 POPEX Module and the D8127/D9127
POPIT Modules to provide eight off-board points (Class B [Style B]) in a single module. You can wire both the
D8128D OctoPOPIT and D8125 POPEX in parallel to the ZONEX Bus Terminals on the same control panel.
1.1

Document Organization

Table 1 identifies the sections of this document.
1.2

Tips, Important Notes, Cautions, and Warnings

Throughout this document, helpful tips, important notes, cautions and warnings are presented for the reader to
keep in mind. These appear different from the rest of the text as follows:
Heed for successful operation and programming. Can also include tips and shortcuts.
Caution the operator that physical damage to the program and/or equipment can occur.
Warn of the possibility of physical damage to the operator, program, and/or equipment.
1.3

Listings

The D8128D is Underwriters Laboratories, Inc. (UL) Listed for Local or Police Connected Burglary Alarm,
Central Station Burglary Alarm, Household Burglary Alarm applications, and Commercial Fire applications
(UL864 and NFPA 72). The D8128D is also suitable for Fire Supervisory applications, such as indicating circuit
supervision using the D192G (D192C) Bell Circuit Supervision Module, sprinkler supervision, and valve tamper
protection.
1.3.1

Requirements for Fire Initiation Applications

You can connect non-powered, fire initiating devices such as pull-stations, heat detectors, and UL Listed four-
wire smoke detectors directly to the D8128D point inputs.
The D125B Dual Powered Loop Interface Module or the D129 Dual Class A Module zone outputs can be
connected directly to the D8128D point inputs. Use the D125B to connect two-wire smoke detectors. Generally,
the D129 is used for connecting waterflow switches.
The D125B or D129 and the OctoPOPIT can be mounted in the same enclosure with the control panel or in a
separate enclosure connected to the control panel's enclosure by conduit no more than 20 ft (6 m) long.
The D7212GV4, D7212GV3, D7212GV2, and D7212G Control Panel is not listed for commercial
fire applications.
F01U070537-07
Section
Description
1
Introduction
2
Overview
3
Installation

Table 1: Document Organization

D8128D Installation Guide