1.0

Introduction

The D8128D OctoPOPIT Module combines the functions of the D8125 POPEX module and the D8127/D9127 POPIT
modules to provide eight off-board points in a single module. You can wire both D8128D OctoPOPIT and D8125
POPEX modules in parallel to the ZONEX Bus terminals on the same panel.
For a list of compatible panels and accessories, please see Section 2.0 D8128D Overview.
1.1

Document Organization

This document is divided into three
sections and an index (refer to Table 1).
1.2

Documentation Conventions

These conventions are intended to call out important features, items, notes, cautions, and warnings that the reader
should be aware of in reading this document.
1.2.1

Tips, Important Notes, Cautions and Warnings

Throughout this document, helpful tips, important notes, cautions and warnings will be presented for the reader to keep
in mind. These appear different from the rest of the text as follows;
Important Notes - should be heeded for successful operation and programming. Also tips and shortcuts may
be included here.
Caution - These caution the operator that physical damage to the program and/or equipment may occur.
Warning - These warn of the possibility of physical damage to the operator, program and/or equipment.
1.3

Listings

The D8128D OctoPOPIT Module is UL Listed for Local or Police Connected Burglary Alarm, Central Station Burglary
Alarm, Household Burglary Alarm applications, and commercial fire applications (UL 864 and NFPA 72). The D8128D is
also suitable for fire supervisory applications, such as indicating circuit supervision (using the D192C Bell Circuit
Supervision Module), sprinkler supervision, and valve tamper protection.
1.3.1

Requirements for Fire Initiation Applications

You may connect non-powered, fire initiating devices such as pull-stations, heat detectors, and UL Listed four-wire
smoke detectors directly to the point inputs on the D8128D.
The D125B Dual Powered Loop Interface Module or the D129 Dual Class "A" Module zone outputs may be connected
directly to the point inputs on the D8128D. Use the D125B to connect 2-wire smoke detectors. Typically, the D129 is
used for connecting waterflow switches.
The D125B or D129 and the OctoPOPIT can be mounted in the same enclosure with the panel or in a separate enclosure
connected to the panel's enclosure by conduit not more than 20 ft. (6 m) in length.
D7212G CONTROL PANEL LISTINGS
The D7212G Control Panel is NOT listed for commercial fire applications.
Application
Note
© 2004 Bosch Security Systems, Inc.
Section
Description
1
Introduction
2
Overview
3
Installation
Index
The index for this installation guide
Table 1: D8128D Installation Guide Organization
D8128D Installation Guide
Page 3
D8128D
Introduction
41343F