Electronic refrigeration control, type ERC 21X

Alarm code

In an alarm situation the display will alternate between readout of the actual air temperature and readout of the
alarm codes of active alarms. Various alarm codes and their descriptions are as below.
Table 37: Alarm codes
Code
Alarms
E29
Sair sensor error
E27
Def sensor error
E30
Sc sensor error
A01
High temp alarm
A02
Low temp alarm
A99
High Volt alarm
AA1
Low Volt alarm
A61
Condenser alarm
A80
Cond. block alarm
A04
Door alarm
A15
DI Alarm
A45
Standby Alarm
(1)
(1)
The condenser block alarm can be reset by setting r12 Main switch OFF and ON again or by powering down the controller.
The condenser block alarm can be reset by setting r12 Main switch OFF and ON again or by powering down the controller.
© Danfoss | Climate Solutions | 2023.01
Description
Air temperature sensor is defect or electrical connection is lost
S5 Evaporator sensor is defect or electrical connection is lost
Sc Condenser sensor is defect or electrical connection is lost
Air temperature in cabinet is too high
Air temperature in cabinet is too low
Supply voltage is too high (compressor protection)
Supply voltage is too low (compressor protection)
Condenser temp. too high - check air flow
Condenser temp. too high - manual reset of alarm required
Door has been open for too long
External alarm from DI input
Control has been stopped by "r12 Main switch"