Supply
Supply voltage range
Frequency tolerance
Typical current consumption
Maximum current consumption
Tightening torque
Stripping length
Nominal cross section
USB 2.0
Connection method
Transmission length
Wireless interface
Interface description
Frequency
EDGE
Digital input
Number of inputs
Electric strength
Switching threshold "0" signal
Switching threshold "1" signal
Switching level "0" signal
Switching level "1" signal
Input current at 250 V AC
107812_en_00
5.4

Technical data

X200
X300
10 V DC ... 60 V DC
-
50 mA
140 mA
(24 V DC)
(24 V DC)
80 mA
180 mA
0.5 Nm ... 0.6 Nm (5-7 lbs-in, screw terminal blocks)
Mini-USB type B, 5-pos.
≤ 3 m (only for configuration and diagnostics)
GSM
850 MHz (2 W (EGSM))
900 MHz (2 W (EGSM))
1800 MHz (1 W (EGSM))
1900 MHz (1 W (EGSM))
Multislot Class 10
X200
X300
Maximum supply voltage
0% ... 30% of the applied
supply voltage
70% ... 100% of the applied
supply voltage
-
-
-
Technical data
X200 AC
X300 AC
93 V AC ... 250 V AC
(47.5 Hz ... 63 Hz)
-15% ... +10% (at 50 Hz and
60 Hz)
15 mA
40 mA
(230 V AC)
(230 V AC)
25 mA
60 mA
7 mm
2.5 mm²
X200 AC
X300 AC
4
-
-
0 V AC ... 50 V AC
90 V AC ... 250 V AC
3.5 mA, typical