Omron E5CC-800 User Manual page 83

Digital temperature controllers
Hide thumbs Also See for E5CC-800:
Table of Contents

Advertisement

Parameters
Characters
alt1
Alarm 1Type
alh1
Alarm 1 Hysteresis
alt2
Alarm 2 Type
alh2
Alarm 2 Hysteresis
alt3
Alarm 3 Type
alh3
Alarm 3 Hysteresis
alt4
Alarm 4 Type
alh4
Alarm 4 Hysteresis
Control Output 1 Signal o1st
Digital Temperature Controllers (Simple Type) User's Manual (H211)
Setting (monitor) value
0: Alarm function OFF
1: Upper and lower-limit alarm
2: Upper-limit alarm
3: Lower-limit alarm
4: Upper and lower-limit range alarm
5: Upper- and lower-limit alarm with standby
sequence
6: Upper-limit alarm with standby sequence
7: Lower-limit alarm with standby sequence
8: Absolute-value upper-limit alarm
9: Absolute-value lower-limit alarm
10: Absolute-value upper-limit alarm with standby
sequence
11: Absolute-value lower-limit alarm with standby
sequence
12: LBA (Loop Burnout Alarm)
13: PV change rate alarm
14: SP absolute-value upper-limit alarm
15: SP absolute-value lower-limit alarm
16: MV absolute-value upper-limit alarm
17: MV absolute-value lower-limit alarm
Temperature input: 0.1 to 999.9 for all alarms except
for MV absolute-value upper-limit or MV lower-limit
alarms
Analog input: 0.01 to 99.99 for all alarms except for
MV absolute-value upper-limit or MV lower-limit
alarms
0.01 to 99.99 for MV absolute-value upper-limit or
MV lower-limit alarms
Same as Alarm 1 Type except that 12 (LBA) cannot
be set.
Temperature input: 0.1 to 999.9 for all alarms except
for MV absolute-value upper-limit or MV lower-limit
alarms
Analog input: 0.01 to 99.99 for all alarms except for
MV absolute-value upper-limit or MV lower-limit
alarms
0.01 to 99.99 for MV absolute-value upper-limit or
MV lower-limit alarms
Same as Alarm 1 Type except that 12 (LBA) cannot
be set.
Temperature input: 0.1 to 999.9 for all alarms except
for MV absolute-value upper-limit or MV lower-limit
alarms
Analog input: 0.01 to 99.99 for all alarms except for
MV absolute-value upper-limit or MV lower-limit
alarms
0.01 to 99.99 for MV absolute-value upper-limit or
MV lower-limit alarms
Same as Alarm 1 Type except that 12 (LBA) cannot
be set.
Temperature input: 0.1 to 999.9 for all alarms except
for MV absolute-value upper-limit or MV lower-limit
alarms
Analog input: 0.01 to 99.99 for all alarms except for
MV absolute-value upper-limit or MV lower-limit
alarms
0.01 to 99.99 for MV absolute-value upper-limit or
MV lower-limit alarms
4-20: 4-20 mA
0-20: 0-20 mA
A Appendices
Display
Default
2
None
°C or °F
0.2
0.02
%FS
0.50
%
2
None
°C or °F
0.2
0.02
%FS
0.50
%
2
None
°C or °F
0.2
0.02
%FS
0.50
%
2
None
°C or °F
0.2
0.02
%FS
0.50
%
4-20, 0-20
4-20
None
Unit
A
A - 15