Connecting Lines to Tension Spring Connection Points

IAS COMPONENTS www.ias-components.com info@ias-components.com
Connect the lines for peripheral equipment and voltage supply to the
tension spring connection points both at the IndraControl L40 and the
Rexroth Inline modules.
Use unshielded lines for the digital inputs and outputs and the voltage
supply. Use shielded lines to connect the analog inputs and outputs.
You can connect lines with a connection cross-section ranging from
0.2 mm² to 1.5 mm² (AWG 24 – 16). These lines permit the supply of
signals of up to 250 V AC/DC and 5 A.
Connecting Unshielded Lines
Fig. 8-12:
Connecting lines to the tension spring connectors
Wire the connectors as required according to your application.
Proceed as follows to wire the connectors:
• Strip the line to a length of 8 mm. Wiring is provided without connector
sleeves. However, connector sleeves may be used, if desired. In this
case, the connector sleeves must be properly crimped.
• Put a screwdriver into the actuation slot of the appropriate terminal
point (Fig. 8-12 , A) as far as necessary to be able to insert the core
into the opening of the spring. Insert the core (Fig. 8-12, B). Pull the
screwdriver out of the opening. This fixes the core. We recommend to
label both the cores and the terminal points after completed
installation.
Note:
For additional information on the connection method, please
refer
to
the
Application
Documentation" on page 1-2).
B
Manual
\2\
Rexroth Inline PROFIBUS DP;
Manual
(see
Chapter
DOK-CONTRL-IC*L40*****-PR02-EN-P
IndraControl L40
A
Zugfederanschluss.FH9
entitled
"Further

Advertisement

Table of Contents
loading

This manual is also suitable for:

Clm40.1-sp-220-na-nnnn-nwClm40.1-np-220-na-nnnn-nw

Table of Contents