Interface For Compact Flash Card; Inline Bus; Functional Module Connector; Fig. 7-26: Ready Led - Bosch Rexroth IndraControl L40 Project Planning Manual

Table of Contents

Advertisement

IndraControl L40

Interface for Compact Flash Card

Compact Flash
7.5

Inline Bus

7.6

Functional Module Connector

DOK-CONTRL-IC*L40*****-PR02-EN-P
IAS COMPONENTS www.ias-components.com info@ias-components.com
The LED arranged next to the Ready contact is a red-green dual LED. It
can assume the following states:
"Ready" LED Meaning
Off
Watchdog not started yet
or
Ready contact opened via the software (but the watchdog is
still triggered internally)
Green
Ready contact closed; watchdogs still triggered.
Red
Ready error; at least one watchdog has responded.
Fig. 7-26:
Ready LED
The IndraControl L40 is provided with a slot for a Compact Flash card.
This slot can be used to insert the memory card containing the firmware
(card to be ordered separately). In addition, data and programs are stored
to this card. Operation without Flash card is not possible.
Operation without memory card causes
uncontrolled movements!
Be sure not to remove the Compact Flash card as
long as the IndraControl L40 is in operation.
DANGER
To its right, the IndraControl L40 can be extended by additional Rexroth
Inline modules. Such modules permit extension of the I/O unit to 32-byte
inputs and 32-byte outputs.
The maximum number of Rexroth Inline modules that can be connected
is 63.
Note:
For further information on the connection of Rexroth Inline
modules, please refer to Chapter "Structure of the Rexroth
Inline Terminals" on page 9-1 and following pages.
To its left, the IndraControl L40 is provided with a functional module
connector that can be used to connect extension modules (in
preparation).
This 120-pin connector is a Bosch Rexroth PC104
the PC104 signals as well as additional system-specific signals are
applied. In other words, only the function modules especially developed
for the IndraControl L40 can be connected to this connector.
Connections and Interfaces