Fig. 7-16: Data Of Digital Outputs - Bosch Rexroth IndraControl L40 Project Planning Manual

Table of Contents

Advertisement

7-10
Connections and Interfaces
IAS COMPONENTS www.ias-components.com info@ias-components.com
Number of outputs
Connection method
Type of outputs
Electric isolation from U
S
Electric isolation from U
L
Output voltage, nominal value
Rated output current
Nominal value
Maximum value according to DIN EN 61131-2
1-signal
0-signal (leakage current)
Maximum total current of outputs
Parallel connection of outputs
Output delay time
Contactor size (at 1 Hz)
Lamp load (at 8 Hz)
Switching frequency
With ohmic load
With inductive load
Overload protection:
Typical current level, causing switchoff
Minimum current level, causing switchoff
Automatic restart with reduced load
Overload indicator
Voltage reduced on circuit interruption in the
nominal operating mode, limited to
Reverse voltage protection
Supply voltage according to EN 61131-2
Open-circuit power consumption from U
Cable length (unshielded)
Fig. 7-16:
Data of digital outputs
Light-emitting diodes indicating the current state of the outputs are
arranged above the output terminals.
LEDs 1, 2, 3, 4
Meaning
Off
The assigned output is not set.
Yellow
The assigned output is set.
Fig. 7-33: Status LEDs of digital outputs
IndraControl L40
8
2-wire connection
Semi-conductor
non-latching
Protected, with automatic
restart
Current-carrying
No
Yes
24 V
0.5 A
≤ 0.6 A
2 mA ... 0.6 A
≤ 0.5 mA
2 A
Yes, but only within one
terminal
< 500
s
µ
SG1 (6.2 W)
5 W
100 Hz
Function (contactor)
1.2 A
0.6 A
After approx. 10 msec
Red collective LED for all 8
outputs
Electronically to (Vext – 50 V)
Typ. 26 V
Ensured without connected
load
24 V DC
Typ. 50 mA
S
< 100 m
DOK-CONTRL-IC*L40*****-PR02-EN-P
outputs,