7-10
Connections and Interfaces
IAS COMPONENTS www.ias-components.com info@ias-components.com
Number of outputs
Connection method
Type of outputs
Electric isolation from U
S
Electric isolation from U
L
Output voltage, nominal value
Rated output current
Nominal value
Maximum value according to DIN EN 61131-2
1-signal
0-signal (leakage current)
Maximum total current of outputs
Parallel connection of outputs
Output delay time
Contactor size (at 1 Hz)
Lamp load (at 8 Hz)
Switching frequency
•
With ohmic load
•
With inductive load
Overload protection:
•
Typical current level, causing switchoff
•
Minimum current level, causing switchoff
•
Automatic restart with reduced load
Overload indicator
Voltage reduced on circuit interruption in the
nominal operating mode, limited to
Reverse voltage protection
Supply voltage according to EN 61131-2
Open-circuit power consumption from U
Cable length (unshielded)
Fig. 7-16:
Data of digital outputs
Light-emitting diodes indicating the current state of the outputs are
arranged above the output terminals.
LEDs 1, 2, 3, 4
Meaning
Off
The assigned output is not set.
Yellow
The assigned output is set.
Fig. 7-33: Status LEDs of digital outputs
IndraControl L40
8
2-wire connection
•
Semi-conductor
non-latching
•
Protected, with automatic
restart
•
Current-carrying
No
Yes
24 V
0.5 A
≤ 0.6 A
2 mA ... 0.6 A
≤ 0.5 mA
2 A
Yes, but only within one
terminal
< 500
s
µ
SG1 (6.2 W)
5 W
100 Hz
Function (contactor)
1.2 A
0.6 A
After approx. 10 msec
Red collective LED for all 8
outputs
Electronically to (Vext – 50 V)
Typ. 26 V
Ensured without connected
load
24 V DC
Typ. 50 mA
S
< 100 m
DOK-CONTRL-IC*L40*****-PR02-EN-P
outputs,