Used With The Ups2000-G-15/20Krtl-01 - Huawei SmartLi-ESM-24020P1 Quick Manual

Table of Contents

Advertisement

SmartLi-ESM-24020P1
Quick Guide
Set the parameters correctly. If the parameters are set incorrectly, the system may
not work properly.
Step 10 Tap Finish. The home screen is displayed.
Step 11 Press and hold the activate button on the front panel of the battery module for
0.5s to disable WiFi. If the WiFi indicator is off, WiFi is disabled successfully. If
there is only one battery module, skip this step.
Step 12 If there are multiple battery modules, perform
module except the last battery module, and perform
battery module.
----End

2.3.2 Used with the UPS2000-G-15/20KRTL-01

Step 1 Check that the following parameters have been set on the LCD of each UPS2000-
G-15/20KRTL-01. Path: Settings > Battery Parameters > Basic
Item
Battery type
Positive batteries
Negative batteries
Battery capacity
Step 2 Use a mobile phone browser to scan the QR code on the front panel of a battery
module to download and install the NetEco app.
Issue 03 (2022-12-30)
NO TICE
NO TE
If battery modules are used with the UPS2000-G-15KRTL-01 or UPS2000-G-20KRTL-01 and
the positive and negative strings of battery modules are separate from each other, you need
to connect to the WiFi network of the positive or negative string to view its information.
Copyright © Huawei Digital Power Technologies Co., Ltd.
2 Power-On Commissioning
Step 3
to
Step 11
Step 3
to
Setting
Lithium battery simulated lead acid
20
20
19 Ah x Number of parallel lithium
batteries in the positive or negative
string/Number of UPSs sharing
batteries
NOTE
For example, if two UPSs sharing batteries
are used and the positive and negative
battery strings each have four batteries, set
Battery capacity to 38 Ah: 19 x 4/2 = 38
Ah
on each battery
Step 10
on the last
55